Hi guys, i have siemens s7-1200 that i need to communicate with. Meanwhile i have programming software Simatic Manager ver.5.3. Can i use this Simatic manager to communicate with s7-1200, and how to configure its connection.
Plc Siemens S7-1200 software download, free. full
- Download software simatic s7-200 for free. Development Tools downloads - STEP 7 MicroWIN by Automation Siemens and many more programs are available for instant and free download.
- The S7-1200 series is a line of programmable logic controllers (PLCs) that can control a variety of automation applications. Compact design, low cost, and a powerful instruction set make the S7-1200 a perfect solution for controlling a wide variety of applications.
Siemens S7 Programming Manual Pdf
plc control system SIMATIC S7-1200, RTD INPUT, SB 1231 RTD, 1 AI RTD, 1 CHANNEL, PT 100 AND PT1000
Supply voltage | |
24 V DC | Yes |
Input current | |
Current consumption, typ. | 5 mA |
from backplane bus 5 V DC, typ. | 20 mA |
Power losses | |
Power loss, typ. | 0.5 W |
Analog inputs | |
Number of analog inputs | 1; Resistance thermometer |
permissible input frequency for current input (destruction limit), max. | ± 35 V |
Technical unit for temperature measurement adjustable | Degrees Celsius/degrees Fahrenheit |
Input ranges | |
Thermocouple | No |
Resistance thermometer | Yes; Platinum (Pt) |
Resistance | Yes; 150 Ω, 300 Ω, 600 Ω |
Input ranges (rated values), voltages | |
Input resistance (-80 mV to +80 mV) | = 10 MOhm”>>= 10 MOhm |
Input ranges (rated values), resistance thermometers | |
Pt 100 | Yes |
Input resistance (Pt 100) | 100 Ω |
Pt 1000 | Yes |
Input resistance (Pt 1000) | 1000 Ω |
Pt 200 | Yes |
Input resistance (Pt 200) | 200 Ω |
Pt 500 | Yes |
Input resistance (Pt 500) | 500 Ω |
Input ranges (rated values), resistors | |
0 to 150 ohms | Yes |
0 to 300 ohms | Yes |
0 to 600 ohms | Yes |
Thermocouple (TC) | |
Temperature compensation | |
Parameterizable | No |
Analog outputs | |
Number of analog outputs | 0 |
Analog value creation | |
Measurement principle | integrating |
Integrations and conversion time/ resolution per channel | |
Resolution with overrange (bit including sign), max. | 15 bit; + sign |
Integration time, parameterizable | No |
Interference voltage suppression for interference frequency f1 in Hz | 85 dB at 10 / 50 / 60 / 400 Hz |
Errors/accuracies | |
Temperature error (relative to input area) | 25 °C ±0.1 % to 55 °C ±0.2 % total measurement range |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | |
Common mode interference, min. | 120 dB |
Interrupts/diagnostics/status information | |
Alarms | |
Alarms | Yes |
Diagnostic alarm | Yes |
Diagnostic messages | |
Diagnostic functions | Yes; Can be read out |
Wire break | Yes |
Diagnostics indication LED | |
for status of the inputs | Yes |
for maintenance | Yes |
Degree and class of protection | |
IP20 | Yes |
Standards, approvals, certificates | |
CE mark | Yes |
C-TICK | Yes |
FM approval | Yes |
Climatic and mechanical conditions for storage and transport | |
Climatic conditions for storage and transport | |
Free fall | |
Drop height, max. (in packaging) | 0.3 m; five times, in dispatch package |
Temperature | |
Permissible temperature range | -40 °C to +70 °C |
Air pressure acc. to IEC 60068-2-13 | |
Permissible air pressure | 1080 to 660 hPa |
Mechanical and climatic conditions during operation | |
Climatic conditions in operation | |
Temperature | |
Permissible temperature range | 0 °C to 55 °C horizontal installation 0 °C to 45 °C vertical installation |
Air pressure acc. to IEC 60068-2-13 | |
Permissible air pressure | 1080 to 795 hPa |
Pollutant concentrations | |
SO2 at RH < 60% without condensation | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free |
Connection method | |
required front connector | Yes |
Mechanics/material | |
Type of housing (front) | |
Plastic | Yes |
Dimensions | |
Width | 38 mm |
Height | 62 mm |
Depth | 21 mm |
Weights | |
Weight, approx. | 35 g |